BRAND : SensorLink

Amp Litewire

Model Number : 8-01513 XT

Fiber optic coupled ammeter, standard sensor

MEASURE PRIMARY CURRENT WAVEFORMS
This probe provides waveform analysis for sophisticated low voltage analyzers, which are otherwise incapable of measuring primary distribution in high voltage
 
FEATURES
Primary distribution probes for CT ratio testing
Supplies an analog output for waveform analysis
Fiber Optic Isolation cable brings the signal to ground
Compatible with most portable test analyzers
 
Range of Operation
Current 1-2000 True RMS Amps
Voltage Environment up to 250 kV
Accuracy ±1%
Frequency: 60Hz (57 to 63) or 50 Hz (47 to 53 Hz) Models available
 
Amp Sensor Opening
Standard Sensor Opening Width: 2.5 in, 6.35 cm
 
Resolution
1-199.9 A:  0.1 A
200 - 2000 A: 1 A
 
Analog Output
1 mv RMS per amp on both the low range and high range
Output connector is BNC. No DC offset voltage
Output impedance
6000 ohms, minimum
 
Frequency Response
3000 Hz or to the 50th Harmonic
 
Fiber Optic Cable
Length 40’, 12.19 m
Isolation 100 kV per foot, 500 kV max
 
Mechanical
Standard Sensor Weight: 4.8 lbs, 2.2 kg
Housing: Shock & water resistant molded urethane
Hot stick Mounting: Universal chuck adapter (hot stick not included)
Battery: Two each 9V alkaline or lithium; one per unit
Battery Life: Minimum 4 hours of continuous use
Operating temperature: -22° to +140° F, -30° to +60° C
Lithium battery required for use below -4°F, -20° C
Display: None; unit must be connected to a power quality analyzer